MIL-DTL-38219D(USAF)
APPENDIX B
B5.2 Option 2. Replace the Existing Meter. This option is recommended, as there will be a small but significant
difference in the readings of the digital millivolt meter and the existing meter when Option 1 is used. Confusion
could arise with both meters operational.
B5.2.1 Remove the existing meter from the Mark 8A TDR. Connect the 1000-ohm resistor between the two leads
that were connected to the existing meter. Connect the digital millivolt meter in parallel with the 1000-ohm resistor.
With the existing meter removed, leads from the TDR to the digital millivolt meter can be brought out through the
front of the TDR, as there will be a 2-inch-diameter hole where the meter was located. If the digital millivolt meter
gives negative readings during calibration, reverse the leads that lead to the digital millivolt meter.
B5.3 It may be possible to find a suitable digital millivolt meter that can be installed within the TDR case in lieu of
the original meter. However, most digital millivolt meters are considerably deeper than the original TDR meter and
there may not be sufficient room to accommodate the new meter within the TDR case. It may be possible, however,
to obtain digital meters which have a detachable display that could be mounted on the front of the TDR with the
remainder of the digital meter located within the TDR case (if there is room) or attached to the side or back of the
TDR.
B5.4 Some users may want to connect the AC power input to the digital meter through the TDR on-off switch.
B6. CALIBRATION
B6.1 The calibration procedure for the digital millivolt meter is the same as for the original meter. The Low Cal and
the High Cal controls are used to adjust the meter readings to agree with the calibration tube ratings as before. Note
the greater sensitivity of the digital millivolt meter may cause some jitter, but this should only be in the tenth of a
millivolt (i.e., TDR unit) range.
B7. OPERATION
B7.1 Mark 8A Tube Deposit Rating Methods. See ASTM D3241, paragraph 9.2.
B7.2 Delta Spun TDR. With the digital millivolt meter, negative TDR readings are possible and the sign (i.e., plus
[+] or minus [-]) of the TDR rating must be recorded as well as the TDR value. The pretest rating must be
algebraically subtracted from the post test rating to obtain the Delta Spun TDR rating. The Delta Spun TDR shall be
determined along the length of the JFTOT tube from position 14 to position 56 at 2-mm increments. The largest
value shall be reported.
16
For Parts Inquires call Parts Hangar, Inc (727) 493-0744
© Copyright 2015 Integrated Publishing, Inc.
A Service Disabled Veteran Owned Small Business